Drinking Water Branch

 

Return Links

 
 Chem/Rad Samples

   Analyte List

 
 Water System Detail

 
 Water Systems

 
 Water System Search

   County Map

Glossary

 

Chem/Rad Sample Results

Water System No. : KY1190061 Federal Type : C
Water System Name : CAMPTON WATER SYSTEM State Type : C
Principal County Served : WOLFE Primary Source : SW
Status : A Activity Date : 06-01-1977
Lab Sample No. : 00080-60702201 Collection Date : 08-15-2006
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1002 ALUMINUM 802 .14  MG/L
1017 CHLORIDE 933 14  MG/L
1022 COPPER, FREE 801 Y MRL 0.01 MG/L 0  MG/L 01-01-2004 12-31-2006
1025 FLUORIDE 807 1.12  MG/L
1028 IRON 801 Y MRL 0.03 MG/L 0  MG/L
1032 MANGANESE 801 Y MRL 0.01 MG/L 0  MG/L
1050 SILVER 801 Y MRL 0.01 MG/L 0  MG/L
1055 SULFATE 944 31.6  MG/L
1095 ZINC 801 Y MRL 0.005 MG/L 0  MG/L
1910 CORROSIVITY 138 1.43  LANG
1920 ODOR 133 1  TON
1925 PH 734 7.18  PH
1930 TDS 806 120  MG/L
2905 FOAMING AGENTS (SURFACTANTS) 855 .03  MG/L

 

 


Total Number of Records Displayed = 14