Drinking Water Branch

 

Return Links

 
 Chem/Rad Samples

 
 Water System Detail

 
 Water Systems

 
 Water System Search

   County Map

Glossary

 

Chem/Rad Sample Results

Water System No. : KY0180549 Federal Type : C
Water System Name : CENTER RIDGE WATER SYSTEM State Type : C
Principal County Served : CALLOWAY Primary Source : GW
Status : A Activity Date : 03-01-1973
Lab Sample No. : L4B0126-01 Collection Date : 02-05-2024
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1017 CHLORIDE 720 N 6.1  MG/L 01-01-2024 12-31-2024
1022 COPPER, FREE 799 N 0.019  MG/L 01-01-2024 12-31-2024
1025 FLUORIDE 720 Y MRL 0.5 MG/L 0.0  MG/L 01-01-2023 12-31-2025
1032 MANGANESE 799 Y MRL 0.05 MG/L 0.0  MG/L 01-01-2024 12-31-2024
1050 SILVER 799 Y MRL 0.016 MG/L 0.0  MG/L 01-01-2024 12-31-2024
1055 SULFATE 720 N 9.3  MG/L 01-01-2024 12-31-2024
1095 ZINC 799 Y MRL 0.02 MG/L 0.0  MG/L 01-01-2024 12-31-2024
1905 COLOR 829 Y MRL 5 CU 0.0  CU 01-01-2024 12-31-2024
1910 CORROSIVITY 838 N -2.94  LANG 01-01-2024 12-31-2024
1919 CALCIUM 799 N 13.00  MG/L
1920 ODOR 833 N 1.0  TON 01-01-2024 12-31-2024
1925 PH 835 N 6.0  PH 01-01-2024 12-31-2024
1930 TDS 806 N 65.00  MG/L 01-01-2024 12-31-2024
1996 TEMPERATURE (CENTIGRADE) 830 N 16.4  C
2905 FOAMING AGENTS (SURFACTANTS) 855 Y MRL 0.2 MG/L 0.0  MG/L 01-01-2024 12-31-2024

 

 


Total Number of Records Displayed = 15